KVL crankcase pressure regulators are used to protect the compressor motor against overload experienced during startup after long off periods or just after defrost periods. They are installed in the suction line of refrigeration systems.
| Product Group : | Pressure Reg - Danfoss |
|---|
KVL crankcase pressure regulators are used to protect the compressor motor against overload experienced during startup after long off periods or just after defrost periods. They are installed in the suction line of refrigeration systems.
| Product Group : | Pressure Reg - Danfoss |
|---|
| Additional Info : | Max. extern.bellow press.25bar |
|---|
| Connection Size : | 1 1/8" | Connection Type : | Solder, ODF |
|---|---|---|---|
| Inlet Connection Size : | 1 1/8 in | Inlet Type : | Solder, ODF |
| Outlet Connection Size : | 1 1/8 in | Outlet Type : | Solder, ODF |
| Model Number : | 034L0046 | Type : | KVL 28 |
|---|
| Kv Value : | 8.000 m³/h |
|---|
| Commodity Code : | 84818059 | Country Of Origin : | POL |
|---|---|---|---|
| EAN : | 5702428411745 | Gross Weight : | 1.014 kg |
| Net Weight : | 0.92 kg |
|---|
| Max Operating Pressure : | 18.0 Bar | Regulating Range : | 0.2-6.0 Bar |
|---|---|---|---|
| Test Pressure : | 19.8 Bar |
| R134a Capacity : | 13.20 kW |
|---|
| R22 Capacity : | 17.80 kW |
|---|
| R407C Capacity : | 16.40 kW |
|---|
| Refrigerant : | R22, R134a, R404A, R407A, R407C, R407F, R407H, R422B, R422D, R448A, R449A, R449B, R450A, R452A, R454A, R454C, R455A, R507A, R513A, R515B, R516A |
|---|
| Approval : | C UL US LISTED, EAC, LLC CDC TYSK, RoHS, RoHS China |
|---|
| Medium Temperature Range : | -60-130 °C |
|---|
| Factory Setting : | 2.00 Bar |
|---|
| CV Value : | 9.250 gal/min | Flow Direction Indicator : | Engraved 1-way arrow |
|---|
| File name | Document Type | Extension | Size |
|---|---|---|---|
| crankcase-pressure-regulator-type-kvl-ast-ai246886497547en-001001.pdf | Technical Literature | 982.28 KB | |
| manufacturer-s-declaration-danfoss-md-034r9541-aa-ast-id365946686609-0101.pdf | Conformity Declaration | 1.04 MB | |
| pressure-regulating-valve-kvp-kvl-kvr-kvd-kvc-ast-an22668643486000-000601.pdf | Installation Manual | 268.01 KB | |
| crankcase-pressure-regulator-type-kvl-ast-ai217486427731en-000701.pdf | Technical Literature | 558.33 KB | |
| manufacturer-s-declaration-danfoss-md-034l9625-ac-ast-id365946844728-0101.pdf | Conformity Declaration | 2.02 MB |